Grounding multiple components in powder processing – Protection from static hazards

Print PDF
User Rating: / 0
PoorBest 

hes dec 18 4Grounding multiple components in powder processing – Protection from static hazards

Powder processing operations can generate vast quantities of electrostatic charge via the movement of powder.

The standard method of charging on powder processing operations is due to tribo-electrification, which is basically the contact and separation of the powder with processing equipment, the powder itself or other factors that can cause charging, like surface contaminants. (Read More) 

There are numerous types of equipment that can cause the charging of powders.

Just some of the processing and handling apparatus that is liable to the risk of static electricity being discharged and, therefore, could ignite the hazardous atmosphere due to a spark include:

  • Pneumatic conveyancing pipes and hoses
  • Micronizers
  • Sieve stacks, sieves and filters
  • Fluid bed dryers
  • Hoppers
  • Dust collectors]Blenders
  • FIBCs
  • Tumbling bins
  • Granulators
  • Totes and drums

Static Grounding protection in powder processing operations

In pharmaceutical operations, equipment like powder conveying systems, micronizers, blenders and sieve stacks all make up multiple component assemblies that can accumulate high levels of electrostatic charge should any of the components be isolated from a true earth ground. Connections made with items like bonding straps can provide an intentional bond between metal components or assembly mating surfaces may provide an inherent bonded connection.

Regular disassembly for cleaning and maintenance can result in bonding connections being missed or not made correctly when the equipment is reassembled. Vibration and corrosion may also degrade assembly connections so it is imperative to ensure that no parts in the assembly become isolated from a true earth ground reference. The most effective way of ensuring that equipment used in powder processing operations cannot accumulate static electricity is to provide a dedicated static grounding solution that will monitor the ground connection of components at risk of static charge accumulation and alert personnel to a potential hazard should a component lose its ground connection. This is especially important if the ground connection point to the equipment is not readily visible or easily accessible.

Static grounding solutions convention versus flexibility

Most grounding solutions provide grounding protection for discrete pieces of equipment at risk of electrostatic charging like road tanker trucks, railcars, IBCs and drums. Powder processing equipment presents more of a challenge as there are many metal parts that can make up larger assemblies that are electrically isolated from each other. It is therefore important to ensure that multiple components that come into contact with charged powders do have a means of being monitored for static grounding protection purposes.

A more specialised static grounding system, like the Earth-Rite® MULTIPOINT II, provides the benefits of eight discrete static grounding systems rolled up into a single package. This gives installer’s the flexibility of providing monitored static grounding protection for multiple components of powder processing assemblies through a discrete wall mounted monitoring unit with eight ground status indicators for each component being monitored.

In addition, the Earth-Rite MULTIPOINT II will continuously check that all components are connected to a reference earth grounding point, thus ensuring that the ground path resistance between the process equipment and the reference ground never exceeds 10 ohms. A monitored ground path resistance of 10 ohms or less is what is recommended in NFPA 77, “Recommended Practice on Static Electricity” and Cenelec CLC/TR 60079-32-1 (2015): Explosive atmospheres - Part 32- 1: Electrostatic Hazards - Guidance.

If the Earth-Rite MULTIPOINT II monitoring unit detects that an assembly component is not grounded, it will send a signal to the controller which, if interlocked with the circuit powering the operation, can halt the process, thereby eliminating the electrostatic charging mechanism and potential charging of un-grounded equipment.

If such an event does occur, the plant’s technicians can rapidly identify which connection needs to be investigated. They can do this by referencing the monitoring unit’s ground status indicator panel which will indicate which channel needs to be checked. Once the connection to the equipment is re-established the Earth-Rite MULTIPOINT II controller will provide a permissive condition for the process to start again.
To download the full application spotlight, with further information on the Earth-Rite® MULTIPOINT II and examples of uses, please visit the Newson Gale website.